Configuration
8200SHB01997-80
Code IMPORTANTPossible settingsNameCode IMPORTANT
InfoChoiceLenze
Name
C036 Voltage/current for
DCB
* 0.00 {0.02 %} 40.00 Page 7-56 *depends on the unit
C037 JOG value 1 20.00 0.00 {0.02 Hz} 480.00 Page 7-43
C038 JOG value 2 30.00 0.00 {0.02 Hz} 480.00 Page 7-43
C039 JOG value 3 40.00 0.00 {0.02 Hz} 480.00 Page 7-43
C050* Output frequency Page 7-62 Display only
C052* Motor voltage Page 7-62 Displayonly[V]
C054* Motor current Page 7-62 Displayonly[A]
C056* Unit load Page 7-62 Displayonly[%]
C061* Heat sink
temperature
Page 7-62 Displayonly[°C]
C079
Oscillation damping * Page 7-31
* depends on the unit
Is not transferred when
821X 82 2x (Software 2x)
82 1x (Software 1x)
822X/824X 82 1x (Software 1x)
C105 Deceleration time
QSP
821X/822X/824X
5.00 0.00 {0.02 s} 999.00
Page 7-55
C106
Holding time for
autom. DC injection
brake
Page 7-56
820X 0.00 0.00 {0.01 s} 50.00
821X/822X
824X
0.02 0.00 {0.01 s} 999.00
C108*
Gain (C111) Page 7-69
820X 220 0 {1} 255
821X/822X/
824X
128 0 {1} 255
C111¤ Monitor signal -0- -0- Field frequency
-1- Unit load
-2- Motor current
-3- DC-bus voltage
Page 7-69