9400 regenerative power supply module | Parameter setting
"CAN on board" system bus
Implemented CANopen objects
156 L EDS94ARNExxxx EN 2.3 - 06/2014
I-1200
Identifier for the SDO server channel 1 (basic SDO channel).
According to DS301 V4.02, the basic SDO channel cannot be changed or deactivated.
[6-9] Assignment of the data telegram
Index:
I-1200
Name:
SDO1 server parameter
Subindex Default setting Display range (min. value | unit | max. value) Access Data type
0: Highest subindex supported 2 2 2 ro U8
1: COB-ID client -> server (rx) Node ID + 0x600 0 4294967295 ro U32
2: COB-ID server -> client (tx) Node ID + 0x580 0 4294967295 ro U32
Subindex Meaning
1 Specification of the receive identifier
For SDO server channel 1: node address (C00350) + 0x600
2 Specification of the transmit identifier
For SDO server channel 1: node address (C00350) + 0x580
8th byte 7th byte 6th byte 5th byte
Data 4 Data 3 Data 2 Data 1
Bit 31 Bit 30 Bit 29 ... bit 11 Bit 10 ... bit 0
0 0 Extended identifier* 11-bit identifier
* The extended identifier is not supported - bits 11 ... 29 must be set to "0".