EDS94ARNExxxx EN 2.3 - 06/2014 L 155
9400 regenerative power supply module | Parameter setting
"CAN on board" system bus
Implemented CANopen objects
I-1018
I-1029
This object serves to set the communication state to which the regenerative power supply
module will change after a bus off, node/life guarding event or heartbeat event.
Index:
I-1018
Name:
Identity object
Subindex Default setting Display range (min. value | unit | max. value) Access Data type
0: Highest subindex supported See below 0 4294967295 ro U32
1: Vendor-ID
2: Product code
3: Revision number
4: Serial number
Subindex Meaning
1 Vendor identification number
• The identification number assigned to Lenze by the "CAN in Automation e. V."
organisation is "0x0000003B".
2 Product code
0x94001 9400 StateLine
0x94002 9400 HighLine
0x94004 9400 regenerative power supply module
3 Main version and subversion of the firmware
4 Serial number
Index:
I-1029
Name:
Error behaviour
Subindex Default setting Setting range (min. value | unit | max. value) Access Data type
0: Highest subindex supported 1 - (read access only) ro U8
1: Communication error 0 0 2 rw U8
Subindex Meaning Lenze code
1 State change after bus off, node/life guarding event or
heartbeat event:
C00625
0 State change from "operational" to "pre-
operational"
1No state change
2 State change to "stopped"