EDS94ARNExxxx EN 2.3 - 06/2014 L 219
9400 regenerative power supply module | Parameter setting
Diagnostics & fault analysis
Error messages
Application has stopped [0x006a000e]
Faulty application parameter [0x006a0010]
Division by zero [0x006a0011]
Pointer access in impermissible memory area [0x006a0012]
Application has started [0x006a0013]
Application has stopped [0x006a0014]
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
The application has been stopped using the device
command C00002
="32". All user tasks are stopped.
Restart application with device command C00002
="31".
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
An invalid parameter description has occurred. Transfer application and parameter set to the
regenerative power supply module again.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
A forbidden division by zero occurred in the application.
The division has been intercepted and the divisor has
been replaced by the value "1".
Exchange application.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
An invalid pointer access to a protected area occurred in
the application.
Exchange application.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
The application in the regenerative power supply
module has been started.
- (Information only)
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
The application in the regenerative power supply
module has been stopped.
- (Information only)