EDS94ARNExxxx EN 2.3 - 06/2014 L 221
9400 regenerative power supply module | Parameter setting
Diagnostics & fault analysis
Error messages
Read error service register [0x00720000]
External error [0x00750000]
Device enabled [0x00750001]
Device: Pulse inhibit is active [0x00750005]
PLC configuration invalid [0x00750006]
Heatsink: Temperature > C00122 [0x00770000]
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
An error has occurred while reading from or writing to
the service register.
Mains switching
Please contact Lenze if the problem occurs again.
Response (Lenze setting printed in bold) Setting: C00581 ( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
The drive interface has activated the error message
"External error".
Check external device to be monitored.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
The regenerative power supply module is enabled and is
in the "Operation" device state.
- (Information only)
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Pulse inhibit is active in the regenerative power supply
module.
- (Information only)
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
An invalid control configuration has occurred. Load another application.
Response (Lenze setting printed in bold) Setting: C00582 ( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Heatsink temperature higher than variable limit
temperature (C00122
).
Ambient device temperature too high.
Dirty fan or ventilation slots.
Value set under C00122 is too low.
Check control cabinet temperature.
Clean filter.
Clean regenerative power supply module.
Set a higher value under C00122
.