212 HVAC Drive H300
Issue Number: 3
Parameter
Range(
Ú) Default(Ö)
Type
OL RFC-A / S OL RFC-A RFC-S
02.001 Post Ramp Reference
VM_SPEED_FREQ_
REF Hz
VM_SPEED_FREQ_
REF rpm
RO Num ND NC PT
02.003 Ramp Hold Off (0) or On (1) Off (0) RW Bit US
02.004 Ramp Mode
Standard (1),
Std boost (2)
Standard (1) Standard (1) RW Txt US
02.006 S Ramp Enable Off (0) or On (1) Off (0) RW Bit US
02.007 Maximum Rate Of Change Of Acceleration
0.0 to 300.0 s
2
/100 Hz 0.000 to 100.000 s
2
/1000 rpm
3.1 1.500 0.030 RW Num US
02.008 Standard Ramp Voltage VM_DC_VOLTAGE_SET V
200 V drive: 375 V
400 V drive 50 Hz: 750 V
400 V drive 60 Hz: 775 V
575 V drive: 895 V
690 V: 1075 V
RW Num RA US
02.009 Deceleration Fail Detection Disable Off (0) or On (1) Off (0) RW Bit US
02.010 Acceleration Rate Selector 0 to 9 0 RW Num US
02.011 Acceleration Rate 1 0.0 to VM_ACCEL_RATE s 0.000 to VM_ACCEL_RATE s 20.0 s 20.000 s RW Num US
02.012 Acceleration Rate 2 0.0 to VM_ACCEL_RATE s 0.000 to VM_ACCEL_RATE s 20.0 s 20.000 s RW Num US
02.013 Acceleration Rate 3 0.0 to VM_ACCEL_RATE s 0.000 to VM_ACCEL_RATE s 20.0 s 20.000 s RW Num US
02.014 Acceleration Rate 4 0.0 to VM_ACCEL_RATE s 0.000 to VM_ACCEL_RATE s 20.0 s 20.000 s RW Num US
02.015 Acceleration Rate 5 0.0 to VM_ACCEL_RATE s 0.000 to VM_ACCEL_RATE s 20.0 s 20.000 s RW Num US
02.016 Acceleration Rate 6 0.0 to VM_ACCEL_RATE s 0.000 to VM_ACCEL_RATE s 20.0 s 20.000 s RW Num US
02.017 Acceleration Rate 7 0.0 to VM_ACCEL_RATE s 0.000 to VM_ACCEL_RATE s 20.0 s 20.000 s RW Num US
02.018 Acceleration Rate 8 0.0 to VM_ACCEL_RATE s 0.000 to VM_ACCEL_RATE s 20.0 s 20.000 s RW Num US
02.020 Deceleration Rate Selector 0 to 9 0 RW Num US
02.021 Deceleration Rate 1 0.0 to VM_ACCEL_RATE s 0.000 to VM_ACCEL_RATE s 20.0 s 20.000 s RW Num US
02.022 Deceleration Rate 2 0.0 to VM_ACCEL_RATE s 0.000 to VM_ACCEL_RATE s 20.0 s 20.000 s RW Num US
02.023 Deceleration Rate 3 0.0 to VM_ACCEL_RATE s 0.000 to VM_ACCEL_RATE s 20.0 s 20.000 s RW Num US
02.024 Deceleration Rate 4 0.0 to VM_ACCEL_RATE s 0.000 to VM_ACCEL_RATE s 20.0 s 20.000 s RW Num US
02.025 Deceleration Rate 5 0.0 to VM_ACCEL_RATE s 0.000 to VM_ACCEL_RATE s 20.0 s 20.000 s RW Num US
02.026 Deceleration Rate 6 0.0 to VM_ACCEL_RATE s 0.000 to VM_ACCEL_RATE s 20.0 s 20.000 s RW Num US
02.027 Deceleration Rate 7 0.0 to VM_ACCEL_RATE s 0.000 to VM_ACCEL_RATE s 20.0 s 20.000 s RW Num US
02.028 Deceleration Rate 8 0.0 to VM_ACCEL_RATE s 0.000 to VM_ACCEL_RATE s 20.0 s 20.000 s RW Num US
02.030 Acceleration Rate Selected 0 to 8 RO Num ND NC PT
02.031 Deceleration Rate Selected 0 to 8 RO Num ND NC PT
02.032 Acceleration Rate Select Bit 0 Off (0) or On (1) Off (0) RW Bit NC
02.033 Acceleration Rate Select Bit 1 Off (0) or On (1) Off (0) RW Bit NC
02.034 Acceleration Rate Select Bit 2 Off (0) or On (1) Off (0) RW Bit NC
02.035 Deceleration Rate Select Bit 0 Off (0) or On (1) Off (0) RW Bit NC
02.036 Deceleration Rate Select Bit 1 Off (0) or On (1) Off (0) RW Bit NC
02.037 Deceleration Rate Select Bit 2 Off (0) or On (1) Off (0) RW Bit NC
02.039 Ramp Rate Units
Off (0) = 100 Hz or
On (1) = Maximum
frequency
Off (0) = 1000 rpm or
1000 mm/s (0) or
On (1) = Maximum speed
On (1) =
Maximum
frequency
On (1) = Maximum
speed
RW Bit US
02.040 S Ramp Percentage 0.0 to 50.0 % 0.0 % RW Num US
02.041 S Ramp Set-up Mode Single (0), Percentage (1) Single (0) RW Txt US
RW Read / Write RO Read only Num Number parameter Bit Bit parameter Txt Text string Bin Binary parameter FI Filtered
ND No default value NC Not copied PT Protected parameter RA Rating dependent US User save PS Power-down save DE Destination