EasyManua.ls Logo

Procentec ComBricks - Page 166

Procentec ComBricks
219 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ComBricks User Manual v6.4.0 | January 18| © PROCENTEC 166/219
Technical Data - 2 Channel Repeater (101-201102)
Cascading depth
Redundancy
Powered according to PB RS-485 (390/220/390 Ohms)
No limit, only busparameter limitation of the master
Yes, maximum 10 cables activated by switch
Dipswitches
NW0 NW1
LEFT LEFT
RIGHT LEFT
LEFT RIGHT
RIGHT RIGHT
RED
LEFT
RIGHT
H/S
LEFT
RIGHT
PROFIBUS Network
1
2
3
4
Redundancy
OFF
ON
Settings
Hardware
Software
PROFIBUS connectors
CH2
A, B
SH
I
CH1
A, B
SH
I
Screw terminals
Green wire, Red wire
Direct grounding
Indirect grounding
Screw terminals + DB9 connector (1-on-1)
Green wire, Red wire
Direct grounding
Indirect grounding
Others
Head Station firmware
Operating temperature
Weight
MTBF
ALL
0 .. 60 °C
125 grams
To be defined
Dipswitches or web
server settings
Redundancy for the
current network
Network 1: NW0 = L, NW1 = L
Network 2: NW0 = R, NW1 = L
Network 3: NW0 = L, NW1 = R
Network 4: NW0 = R, NW1 = R
Channel 1 and
Channel 2
Channel 2 and
Channel 1
Communication
error on Channel x
Termination ON
on Channel x
Data received on
Channel x
Repeater Module
status
Network 1: NW0 = L, NW1 = L
Network 2: NW0 = R, NW1 = L
Network 3: NW0 = L, NW1 = R
Network 4: NW0 = R, NW1 = R

Table of Contents