ComBricks User Manual v6.4.0 | January 18| © PROCENTEC 178/219
Technical Data - Alternative Cable Repeater (101-201710)
Termination range (MIDDLE)
Idle voltage range (PULL-UP)
94 .. 940 Ohm (DC) 57 .. 1500 Ohm (AC)
0 .. 5 V
Dipswitches
NW0 NW1
LEFT LEFT
RIGHT LEFT
LEFT RIGHT
RIGHT RIGHT
RED
LEFT / RIGHT
H/S
LEFT / RIGHT
PROFIBUS Network
1
2
3
4
Redundancy
OFF / ON
Settings
Hardware / Software
PROFIBUS connectors
CH1
A, B
SH
I
Screw terminals
Green wire, Red wire
Direct grounding
Indirect grounding
LEDs
RDY
RX
HWE
ER
MIN
TERM
Module is ready for operation (ON)
Receiving telegrams (blinking)
Internal repeater error (contact PROCENTEC)
No or bad telegrams detected
Signal amplitude of the telegrams too low ( < 2.5 V )
Idle voltage too low ( <0.5 V .. >1.7 V )
Alarm values can be changed through the web server.
Others
Head Station firmware
Operating temperature
Weight
MTBF
At least version 1.264
0 .. 60 °C
120 g
To be defined
Dipswitches or web
server settings
Redundancy for the
current network
Communication
error or bad
telegrams
Data received
Repeater Module
status
Network 1: NW0 = L, NW1 = L
Network 2: NW0 = R, NW1 = L
Network 3: NW0 = L, NW1 = R
Network 4: NW0 = R, NW1 = R
Repeater internal
failure
The idle voltage
when nobody is
sending is too low
Signal amplitude of
the telegrams
is too low