SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 271
Code Name Causes Possible Solutions
EF6 External Fault (Terminal DI6)
MFDI terminal DI6 caused an external fault through
an external device.
1. Find the device that caused the external fault and remove the
cause.
2. Clear the external fault input in the MFDI.
The wiring is incorrect. Correctly connect the signal line to MFDI terminal DI6.
External Fault [H1-06 = 20 to 2B] is set to MFDI
terminal DI6, but the terminal is not in use.
Correctly set the MFDI.
Note:
Do a Fault Reset to clear the fault.
Code Name Causes Possible Solutions
EF7 External Fault (Terminal DI7)
MFDI terminal DI7 caused an external fault through
an external device.
1. Find the device that caused the external fault and remove the
cause.
2. Clear the external fault input in the MFDI.
The wiring is incorrect. Correctly connect the signal line to MFDI terminal DI7.
External Fault [H1-07 = 20 to 2B] is set to MFDI
terminal DI7, but the terminal is not in use.
Correctly set the MFDI.
Note:
Do a Fault Reset to clear the fault.
Code Name Causes Possible Solutions
EF8 External Fault (Terminal DI8)
MFDI terminal DI8 caused an external fault through
an external device.
1. Find the device that caused the external fault and remove the
cause.
2. Clear the external fault input in the MFDI.
The wiring is incorrect. Correctly connect the signal line to MFDI terminal DI8.
External Fault [H1-08 = 20 to 2B] is set to MFDI
terminal DI8, but the terminal is not in use.
Correctly set the MFDI.
Note:
Do a Fault Reset to clear the fault.
Code Name Causes Possible Solutions
Err EEPROM Write Error
There was a problem with the EEPROM hardware. Re-energize the drive.
If the fault stays, replace the control board or the drive. For
information about replacing the control board, contact the
manufacturer or your nearest sales representative.
Electrical interference corrupted the data while it
was writing to the EEPROM of the drive.
Push .
Set the parameters again.
Note:
Do a Fault Reset to clear the fault.
Code Name Causes Possible Solutions
FAn Internal Fan Fault
The circulation fan stopped operating correctly. Examine circulation fan operation.
Re-energize the drive.
Check U4-03 [Fan Oper.Time] and U4-04 [Cool Fan
Maintenance]. If the performance life of the circulation fan is
expired or if there is damage to the fan, replace the fan.
There is a problem with the power supply of the
electromagnetic contactor and the circulation fan.
1. Re-energize the drive.
2. If the fault stays, replace the control board or the drive. For
information about replacing the control board, contact the
manufacturer or your nearest sales representative.
Note:
Do a Fault Reset to clear the fault.
Code Name Causes Possible Solutions
FAn1 Drive Cooling Fan Fault
The cooling fan stopped operating correctly. Examine cooling fan operation.
Re-energize the drive.
Check U4-03 [Fan Oper.Time] and U4-04 [Cool Fan
Maintenance]. If the performance life of the cooling fan is
expired or if there is damage to the fan, replace the fan.
Note:
Do a Fault Reset to clear the fault.
Code Name Causes Possible Solutions
FbH Excessive PID Feedback
The FbH detection level is set incorrectly. Adjust b5-36 [PID HiHi Limit Level] and b5-37 [PID HiHi
Time].
There is a problem with the PID feedback wiring. Correct errors with the PID control wiring.
The feedback sensor is not operating correctly. Examine the sensors on the control device side.