Parameter Details
12
12.8 L: PROTECTION
SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 803
L8-93 Lso Detect Time
No.
(Hex.)
Name Description
Default
(Range)
L8-93
(073C)
Expert
Lso Detect Time
Sets the length of time the drive will wait to start baseblock after detecting LSo [LSo Fault].
1.0 s
(0.0 - 10.0 s)
Set this parameter to 0.0 to disable the function.
L8-94 Lso Detect Level
No.
(Hex.)
Name Description
Default
(Range)
L8-94
(073D)
Expert
Lso Detect Level
Sets the detection level for LSo [Low Speed Motor Step-Out] as a percentage of E1-04 [Max
Output Frequency].
3%
(0 - 10%)
L8-95 Lso Amount
No.
(Hex.)
Name Description
Default
(Range)
L8-95
(077F)
Expert
Lso Amount
Sets the average count of LSo [Low Speed Motor Step-Out] detections.
10 times
(1 - 50 times)
L9: DRIVE PROTECTION 2
L9 parameters are used to configure the protection function used to detect cooling fan faults.
L9-16 FAn1 Detect Time
No.
(Hex.)
Name Description
Default
(Range)
L9-16
(11DC)
Expert
FAn1 Detect Time
Sets the detection time for FAn1 [Drive Cooling Fan Failure]. The manufacturer recommends
that you do not change this parameter value.
4.0 s
(0.0 - 30.0 s)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents