EasyManua.ls Logo

Q2 Q2A - L9: Drive Protection 2

Q2 Q2A
866 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Details
12
12.8 L: PROTECTION
SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 803
L8-93 Lso Detect Time
No.
(Hex.)
Name Description
Default
(Range)
L8-93
(073C)
Expert
Lso Detect Time
Sets the length of time the drive will wait to start baseblock after detecting LSo [LSo Fault].
1.0 s
(0.0 - 10.0 s)
Set this parameter to 0.0 to disable the function.
L8-94 Lso Detect Level
No.
(Hex.)
Name Description
Default
(Range)
L8-94
(073D)
Expert
Lso Detect Level
Sets the detection level for LSo [Low Speed Motor Step-Out] as a percentage of E1-04 [Max
Output Frequency].
3%
(0 - 10%)
L8-95 Lso Amount
No.
(Hex.)
Name Description
Default
(Range)
L8-95
(077F)
Expert
Lso Amount
Sets the average count of LSo [Low Speed Motor Step-Out] detections.
10 times
(1 - 50 times)
L9: DRIVE PROTECTION 2
L9 parameters are used to configure the protection function used to detect cooling fan faults.
L9-16 FAn1 Detect Time
No.
(Hex.)
Name Description
Default
(Range)
L9-16
(11DC)
Expert
FAn1 Detect Time
Sets the detection time for FAn1 [Drive Cooling Fan Failure]. The manufacturer recommends
that you do not change this parameter value.
4.0 s
(0.0 - 30.0 s)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents