Parameter Details
12
12.10 o: KEYPAD
SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 839
When you replace a drive, set o4-07 = 0 to reset the value of U4-06. When the o4-07 setting changes the count of
U4-06 starts again as specified by the setting of o4-07. After you complete the configuration, the setting value of
o4-07 automatically resets to 0.
Note:
The maintenance period changes for different operating environments.
■ o4-09 IGBT Preset Maintenance Cnt
No.
(Hex.)
Name Description
Default
(Range)
o4-09
(0525)
IGBT Preset Maintenance
Cnt
Sets the U4-07 [IGBT Maintenance] monitor value.
0%
(0 - 150%)
When you replace a drive, set o4-09 = 0 to reset the value of U4-07. When the o4-09 setting changes the count of
U4-07 starts again as specified by the setting of o4-09. After you complete the configuration, the setting value of
o4-09 automatically resets to 0.
Note:
The maintenance period changes for different operating environments.
■ o4-11 Flt.History Initialization
No.
(Hex.)
Name Description
Default
(Range)
o4-11
(0510)
Flt.History Initialization
Resets the records of Monitors [U2: FAULT] and [U3: FAULT HISTORY].
0
(0, 1)
Note:
When you initialize the drive with A1-03 [Init Parameters], the drive will not reset the records for U2-xx and U3-xx.
0 : No Reset
Keeps the records of Monitors U2-xx and U3-xx.
1 : Reset
Resets the records for Monitors U2-xx and U3-xx. After the reset, the drive automatically resets o4-11 to 0.
■ o4-12 kWh Monitor Initialization
No.
(Hex.)
Name Description
Default
(Range)
o4-12
(0512)
kWh Monitor Initialization
Resets the monitor values for U4-10 [kWh Lower 4Digits] and U4-11 [kWh Upper 5Digits].
0
(0, 1)
Note:
When you initialize the drive with A1-03 [Initialize Parameters], the drive will not reset U4-10 and U4-11.
0 : No Reset
Keeps the monitor values for U4-10 and U4-11.
1 : Reset
Resets the values of U4-10 and U4-11. After the reset, the drive automatically resets o4-12 to 0.
■ o4-13 NumOfRunCom Init Counter
No.
(Hex.)
Name Description
Default
(Range)
o4-13
(0528)
NumOfRunCom Init
Counter
Resets the monitor values for U4-02 [Num of Run Commands], U4-24 [No of Travels(L)], and
U4-25 [No of Travels(H)].
0
(0, 1)
0 : No Reset
Keeps the monitor values for U4-02, U4-24, and U4-25.
1 : No Reset
Resets the values of U4-02, U4-24, and U4-25. After the reset, the drive automatically resets o4-13 to 0.