4. BASIC OPERATION
IMR02L04-E3
4-43
Continued from the previous page.
Name Symbol Data range
Factory set
value
Function block 61 (F61.01 to F61.06)
Slave controller
SLV.SL
0: FB series: FB100/400/900
1: RB series: RB100/400/500/700/900
2: PF900/901
0
Number of slave unit
SLV.NO
0 to 4 0
Device address 2 *
ADD2
0 to 99 0
Communication speed 2 *
BPS2
9600: 9600 bps
19200: 19200 bps
38400: 38400 bps
19200
Host communication error judgment
time
H.ER.TM
0 to 600 seconds
0: Unused
10
Intercontroller communication error
judgment time
C.ER.TM
0 to 600 seconds
0: Real-time error
10
Function block 71 (F71.01, F71.02)
Setting limiter high
SLH
Setting limiter low to Input range high
(The unit is the same as input value)
Input range
high
Setting limiter low
SLL
Input range low to Setting limiter high
(The unit is the same as input value)
Input range
low
Function block 80 (F80.01 to F80.07)
SV selection at Program start *
ST.SV
0: Start with the Set value (SV) in the Reset mode.
1: PV start 1 [Time fixed type]
2: PV start 2 [Time saving & ramp holding type]
3: PV start 3 [Time saving & level searching type/
With HOLD function at start]
4: PV start 4 [Time saving & level searching type/
Without HOLD function at start]
2
Wait memory group number at
Program start
ST.WT
0: Wait OFF
1 to 8: Wait memory 1 to Wait memory 8
0
Program setting type
PR.TYP
0: Batch setting type
1: Partial setting type
1
Signal type
TS.TYP
0: Time signal type
1: Segment signal type
0
Set time unit
TM.SL
0: Hou
: Minute
1: Minute
: Secon
0
Maximum pattern/segment number
PNŠSN
Maximum pattern number: 1 to 99
Maximum segment number: 1 to 99
Maximum pattern number Maximum segment number
1024 at maximum
Maximum
pattern
number: 32
Maximum
segment
number: 32
* It is not necessary to change the operation mode to the Reset mode (RESET) when setting the parameters. The parameters may
also be set in the Setup setting mode.