5. OPERATION
IMR02L04-E3
5-6
5.1.4 Check set value of parameter for program control operation
Parameter settings related to Program control operation can be checked at F80 in Engineering mode.
PV
F80.
M:S
SV
FIX000VPROG
Function block 80
(F80.)
PV
S ST.SV
M:S
SV
F80.01R 00002
SV selection at
Program start
PV
PNŠSN
M:S
SV
F80.06R 32Š32
Maximum pattern
number
Setup example:
Number of program pattern: 32
Number of segment: 32
PV
PNŠSN
M:S
SV
F80.07R 32Š32
Maximum segment
number
Set parameters for Program operation after confirming
parameter of control action.
PV
F50.
M:S
SV
FIX000CONTR
Function block 50
(F50.)
Press the
key until F80
displays.
Select SV at program start.
00000: Start with the Set value (SV) in the Reset mode.
00001: PV start 1 [Time fixed type]
00002: PV start 2 [Time saving & ramp holding type]
(Factory set value)
00003: PV start 3 [Time saving & level searching type/
With HOLD function at start]
00004: PV start 4 [Time saving & level searching type/
Without HOLD function at start]
PV
S ST.WT
M:S
SV
F80.02R 00000
Wait memory group
number at Program start
Select Wait memory group number at
program start.
00000: Wait OFF (Factory set value)
00001 to 00008:
Wait memory 1 to
Wait memory 8
PV
PR.TYP
M:S
SV
F80.03R 00001
Program setting type
Select Program setting type.
00000: Batch setting type
00001: Partial setting type
(Factory set value)
PV
TS.TYP
M:S
SV
F80.04R 00000
Signal type
Select Signal type.
00000: Time Signal type
(Factory set value)
00001: Segment Signal type
PV
T TM.SL
M:S
SV
F80.05R 00000
Set time unit
Select Set time unit of program.
00000: Hour : Minute
(Factory set value)
00001: Minute : Second
Set Maximum pattern number.
[Range: 1 to 99]
Factory set value: 32
Set Maximum segment number.
[Range: 1 to 99]
Factory set value: 32
Maximum pattern number
Maximum segment number
Maximum pattern nu
m
b
er x Maximum segment number = 1024 maximum
Return to
Function block 80
(F80.)
When changing a Maximum pattern number or Maximum segment number, all parameters related
to Program setting such as Segment level and Segment time will be initialized automatically.
Parameter to be initialized
Parameter setting mode: SV setting mode:
Parameter at Program setting block Execution pattern number
Wait zone high and Wait zone low at the Wait memory group setting block Setting by RKC communication:
Output program value from 1 to 3 at the Output program memory group setting block Pattern tag name
Parameter at the Time signal memory group setting block
(P. 4-41)
(P. 4-43)

Table of Contents

Other manuals for RKC INSTRUMENT PF900

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the RKC INSTRUMENT PF900 and is the answer not in the manual?

RKC INSTRUMENT PF900 Specifications

General IconGeneral
BrandRKC INSTRUMENT
ModelPF900
CategoryController
LanguageEnglish

Related product manuals