54 Rockwell Automation Publication 450L-UM001D-EN-P - December 2019
Chapter 4 Safety Function
Advanced Feature Response Time, T
a
The response time of advanced features requires a complex algorithm. The
response time is also dependent upon whether the features are set up the DIP
switches on the plug-in or software configured by Connected Components
Workb en c h so ft wa re.
Tabl e 17
shows response times when the advanced features are set by the Dip
switches on the blanking or muting plug-in. The description of each column is:
Column Description Column Description
1 Standard operation with beam coding 7 Reduced resolution, two beams with beam coding
2 Fixed blanking up to four zones 8 Fixed blanking up to four zones + reduced resolution, single beam
3 Fixed blanking up to four zones with beam coding 9 Fixed blanking up to four zones + reduced resolution, single beam with beam coding
4 Reduced resolution, single beam 10 Fixed blanking up to four zones + reduced resolution, two beams
5 Reduced resolution, single beam with beam coding
11 Fixed blanking up to four zones + reduced resolution, two beams with beam coding
6 Reduced resolution, two beams
Table 17 - Response Time, T
a
(Set by DIP Switches)
Response Time, T
a
, (ms)
Protective
Height
[mm (in)] 1234567891011
Finger Resolution
150 (5.91) 9 14161213151617191820
300 (11.81) 1115171314171819202021
450 (17.72) 1317191516181920222123
600 (23.62) 1418201618192121232224
750 (29.53) 1519211718202123242425
900 (35.43) 1519211718202123242425
1050 (41.34) 1619221720202323262427
1200 (47.24) 1820241821212423272428
1350 (53.15) 1921261923222624292530
1500 (59.06) 2122272024232725302731
1650 (64.96) 2223292126242927322833
1800 (70.87) 2425302327263028332934
1950 (76.77) 2526322429273229353036