4.109
Date Code 20081022 Instruction Manual SEL-787 Relay
Protection and Logic Functions
DNP Map Settings (SET DNP n Command, n = 1, 2, or 3)
DNP Map Settings (SET DNP n Command, n = 1, 2, or 3)
Table 4.65 shows the available settings. See Appendix D: DNP3
Communications for additional details.
Table 4.65 DNP Map Settings
a
a
See Appendix D: DNP3 Communications for complete list of the DNP Map Labels and
factory default settings.
Setting Prompt Setting Range
Setting Name := Factory
Default
DNP Binary Input Label Name 10 characters BI_00 := ENABLED
DNP Binary Input Label Name 10 characters BI_01 := TRIPXFMR
DNP Binary Input Label Name 10 characters BI_02 := TRIP1
DNP Binary Input Label Name 10 characters BI_03 := TRIP2
·
·
·
DNP Binary Input Label Name 10 characters BI_99 := NA
DNP Binary Output Label Name 10 characters BO_00 := RB01
·
·
·
DNP Binary Output Label Name 10 characters BO_31 := RB32
DNP Analog Input Label Name 24 characters AI_00 := IAW1_MAG
DNP Analog Input Label Name 24 characters AI_01 := IBW1_MAG
·
·
·
DNP Analog Input Label Name 24 characters AI_99 := NA
DNP Analog Output Label Name 6 characters AO_00 := NA
·
·
·
DNP Analog Output Label Name 6 characters AO_31 := NA
DNP Counter Label Name 11 characters CO_00 := NA
·
·
·
DNP Counter Label Name 11 characters CO_31 := NA