F.26
SEL-787 Relay Instruction Manual Date Code 20081022
IEC 61850 Communications
ACSI Conformance Statements
ACSI Conformance Statements
Table F.27 ACSI Basic Conformance Statement
Client/Subscriber Server/Publisher SEL-787 Support
Client-Server Roles
B11 Server side (of Two-Party
Application-Association)
-cl
a
YES
B12 Client side (of Two-Party
Application-Association)
cl
a
a
c1 shall be mandatory if support for LOGICAL-DEVICE model has been declared.
-
SCMS Supported
B21 SCSM: IEC 61850-8-1 used
YES
B22 SCSM: IEC 61850-9-1 used
B23 SCSM: IEC 61850-9-2 used
B24 SCSM: other
Generic Substation Event Model (GSE)
B31 Publisher side
-O
b
YES
B32 Subscriber side
O
b
b
O = optional.
-YES
Transmission of Sampled Value Model (SVC)
B41 Published side
-O
b
B42 Subscriber side
O
b
-
Table F.28 ACSI Models Conformance Statement (Sheet 1 of 2)
Client/Subscriber Server/Publisher SEL-787 Support
If Server Side (B11) Supported
M1 Logical device
c2
a
c2
a
YES
M2 Logical node
c3
b
c3
b
YES
M3 Data
c4
c
c4
c
YES
M4 Data set
c5
d
c5
d
YES
M5 Substation
O
e
O
e
M6 Setting group control
O
e
O
e
Reporting
M7 Buffered report control
O
e
O
e
YES
M7-1 sequence-number
YES
M7-2 report-time-stamp
YES
M7-3 reason-for-inclusion
YES
M7-4 data-set-name
YES
M7-5 data-reference
YES