F.10
SEL-787 Relay Instruction Manual Date Code 20081022
IEC 61850 Communications
IEC 61850 Operation
The SEL-787 will transmit all configured GOOSE immediately
upon successful initialization. If a GOOSE is not retriggered,
then, following initial transmission, the SEL-787 will
retransmit that GOOSE on a curve. The curve begins at 10 ms
and doubles for each retransmission until leveling at the
maximum specified in the CID file for that GOOSE. For
example, a message with a maximum retransmit interval of 100
ms is retransmitted at intervals of 10 ms, 20 ms, 40 ms, 80 ms,
and 100 ms, then repeated every 100 ms until a trigger causes
the transmission sequence to be repeated. The time-to-live
reported in each transmitted message, is three times the current
interval, or two times the interval, if the maximum time-to-live
has been reached (30 ms, 60 ms, 120 ms, 240 ms, and 200 ms
for the example above; see IEC 61850-8-1, sec. 18.1).
GOOSE transmission is squelched (silenced) after a permanent
(latching) self-test failure.
Each outgoing GOOSE includes communication parameters
(VLAN, Priority, and Multicast Address) and is transmitted
entirely in a single network frame.
The SEL-787 will maintain the configuration of outgoing
GOOSE through a power cycle and device reset.
Incoming GOOSE messages are processed in accordance with the following
constraints:
The user can configure the SEL-787 to subscribe to as many as
16 incoming GOOSE messages.
The SEL-787 will recognize incoming GOOSE messages as
valid based on the following content. Any GOOSE message
that fails these checks shall be rejected.
Source broadcast MAC address
Dataset Reference
Application ID
GOOSE Control Reference
Rejection of all DA contained in an incoming GOOSE, based
on the accumulation of the following error indications created
by inspection of the received GOOSE:
Configuration Mismatch: the configuration number of
the incoming GOOSE changes.
Needs Commissioning: this Boolean parameter of the
incoming GOOSE is true.
Test M od e: this Boolean parameter of the incoming
GOOSE is true.
Decode Error: the format of the incoming GOOSE is
not as configured.
The SEL-787 will discard incoming GOOSE under the
following conditions:
after a permanent (latching) self-test failure
when EGSE is set to No
Link-layered priority tagging and virtual LAN is supported as described in
Annex C of IEC 61850-8-1:2004(E).