3-30 Overcurrent, Voltage, Synchronism Check, and Frequency Elements Date Code 990430
SEL-351P Manual Técnico
Table SECTION 3: .8: Voltage Elements Settings and Settings Ranges
Voltage Element
(Relay Word bits)
Operating
Voltage
Pickup Setting/Range See Figure
27A1 V
A
27P1P Figure SEC
TION 3:
.21
27B1 V
B
0.0 - 150.0 V secondary
27C1 V
C
3P27 = 27A1 * 27B1 * 27C1
27A2 V
A
27P2P
27B2 V
B
0.0 - 150.0 V secondary
27C2 V
C
59A1 V
A
59P1P
59B1 V
B
0.0 - 150.0 V secondary
59C1 V
C
3P59 = 59A1 * 59B1 * 59C1
59A2 V
A
59P2P
59B2 V
B
0.0 - 150.0 V secondary
59C2 V
C
27AB V
AB
27PP Figure SEC
TION 3:
.22
27BC V
BC
0.0 - 260.0 V secondary
27CA V
CA
59AB V
AB
59PP
59BC V
BC
0.0 - 260.0 V secondary
59CA V
CA
59N1
3V
0
59N1P
0.0 - 150.0 V secondary
59N2 3V
0
59N2P
0.0 - 150.0 V secondary
59Q V
2
59QP
0.0 - 100.0 V secondary
59V1 V
1
59V1P
0.0 - 150.0 V secondary
27S V
S
27SP
0.0 - 150.0 V secondary
Figure SEC
TION 3:
.23

Table of Contents