EasyManua.ls Logo

Schweitzer Engineering SEL-351P - Page 329

Default Icon
674 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Date Code 990215 Inputs, Outputs, Timers, and Other Control Logic 7-5
SEL-351P Manual Técnico
The pickup/dropout timer for input IN102 (IN102D) is set at:
IN102D = 1.00 cycle
to provide input energization/deenergization debounce.
E
XTRA
L
OCAL
C
ONTROL
S
WITCHES
The local control switch feature of this relay replaces traditional panel-mounted control switches.
Operate the eight (8) local control switches using the front-panel keyboard/display (see
Section 11: Additional Front-Panel Interface Details). This extra local control is not the
control available via the operator control pushbuttons on the bottom half of the SEL-351P front
panel.
Figure SECTION 7: .3: Local Control Switches Drive Local Bits LB1 Through LB8
The output of the local control switch in
Figure SECTION 7: .3 is a Relay Word bit LBn (n = 1
through 8), called a local bit. The local control switch logic in
Figure SECTION 7: .3 repeats
for each local bit LB1 through LB8. Use these local bits in SEL
OGIC
Control Equations. For a
given local control switch, the local control switch positions are enabled by making
corresponding label settings.

Table of Contents