9-28 Setting the SEL-351P Recloser Control Date Code 990430
SEL-351P Manual Técnico
Row
Bit
Definition
Primary
Application
32VE Internal enable for zero-sequence voltage-polarized,
residual-current directional element (see Figures 4.4,
4.8, and 4.10)
32QGE Internal enable for negative-sequence voltage-
polarized directional element (for ground; see
Figures 4.4, 4.5, and 4.8)
32NE Internal enable for zero-sequence voltage-polarized,
neutral-current directional element (see Figures 4.4,
4.7, and 4.11)
32QE Internal enable for negative-sequence voltage-
polarized directional element (see Figures 4.4, 4.5,
and 4.17)
16 F32P
R32P
F32Q
R32Q
F32QG
R32QG
F32V
R32V
Forward positive-sequence voltage-polarized
directional element (see Figures 4.18 and 4.19)
Reverse positive-sequence voltage-polarized
directional element (see Figures 4.18 and 4.19)
Forward negative-sequence voltage-polarized
directional element (see Figures 4.17 and 4.19)
Reverse negative-sequence voltage-polarized
directional element (see Figures 4.17 and 4.19)
Forward negative-sequence voltage-polarized
directional element (for ground; see Figures 4.4, 4.9,
4.12, and 4.13)
Reverse negative-sequence voltage-polarized
directional element (for ground; see Figures 4.4, 4.9,
4.12, and 4.13)
Forward zero-sequence voltage-polarized, residual-
current directional element (see Figures 4.4, 4.10,
4.12, and 4.13)
Reverse zero-sequence voltage-polarized, residual-
current directional element (see Figures 4.4, 4.10,
4.12, and 4.13)
Testing, Special
directional
control schemes
17 F32N Forward zero-sequence voltage-polarized, neutral
current directional element (see Figures 4.4, 4.11,
and 4.13)
R32N Reverse zero-sequence voltage-polarized, neutral
current directional element (see Figures 4.4, 4.11,
and 4.13)
32PF Forward directional control routed to phase
overcurrent elements (see Figures 4.19 and 4.21)