Date Code 990430 Serial Port Communications and Commands 10-33
SEL-351P Manual Técnico
Continued from Previous Page
SS5 =0
SS6 =0
ER =/51P1 + /51P2 + /51G1 + /51G2 + /51N1 + /51N2 + /67N3
FAULT =51P1 + 51P2 + 51G1 + 51G2 + 51N1 + 51N2 + 67N3
BSYNCH=52A
CLMON =0
BKMON =WBTR + WBTRT + \52A
E32IV =1
Press RETURN to continue
TMB1A = 0
TMB2A = 0
TMB3A = 0
TMB4A = 0
TMB5A = 0
TMB6A = 0
TMB7A = 0
TMB8A = 0
TMB1B = 0
TMB2B = 0
TMB3B = 0
TMB4B = 0
TMB5B = 0
TMB6B = 0
TMB7B = 0
TMB8B = 0
=>>
=>>SHO P <ENTER>
Port 3
PROTO = SEL
SPEED = 2400 BITS = 8 PARITY= N STOP = 1
T_OUT = 15 AUTO = N RTSCTS= N FASTOP= N
=>>SHO R <ENTER>
Sequential Events Recorder trigger lists:
SER1 =TRIP 51P1T 51P2T 51G1T 51G2T 51N1T 51N2T 67P2T 67G2T 67N2T 67N3T
81D1T PB9 67P1 67G1 67N1
SER2 =CLOSE 52A CF 79CY 79LO 79RS SH0 SH1 SH2 SH3 SH4 PB8 59A1
SER3 =TOSLP BCBOK DTFAIL
Load Profile settings: (Only available in firmware versions 1 and greater)
LDLIST=0
LDAR = 5
=>>