EasyManua.ls Logo

Schweitzer Engineering SEL-351P - Page 632

Default Icon
674 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Date Code 990215 Setting Negative-Sequence Overcurrent Elements F-5
SEL-351P Manual Técnico
Figure APPENDIX F: .3 shows traditional phase overcurrent element coordination between the
feeder relay and line recloser phase overcurrent elements. Phase overcurrent elements must
accommodate load and cold load pickup current. The 450 A maximum feeder load current limits
the sensitivity of the feeder phase overcurrent element, 51F, to a pickup of 600 A. The feeder
relay cannot back up the line recloser for phase faults below 600 A.
Apply the Feeder Relay Negative-Sequence Overcurrent Element (Guidelines 1 to 3)
Applying negative-sequence overcurrent element coordination Guidelines 1 to 3 results in the
feeder relay “equivalent” phase overcurrent element (51EP) in
Figure APPENDIX F: .4. Curve
for 51F is shown for comparison only.
Figure APPENDIX F: .4: Phase-to-Phase Fault Coordination
51EP: pickup = 300 A (below max. feeder load, I
F
)
Considerable improvement in sensitivity and speed of operation for phase-to-phase faults is
achieved with the 51EP element. The 51EP element pickup of 300 A has twice the sensitivity of
the 51F element pickup of 600 A. The 51EP element speed of operation for phase-to-phase
faults below about 2000 A is faster than that for the 51F element.
Convert “Equivalent” Phase Overcurrent Element Settings to Negative-
Sequence Overcurrent Element Settings (Guideline 4)
The “equivalent” phase overcurrent element (51EP element in Figure APPENDIX F: .4)
converts to true negative-sequence overcurrent element settings (51QF in
Figure APPENDIX F:
.5) by applying the equation given in Guideline 4. The time dial (lever) and curve type of the

Table of Contents