Response Description
Rapid stop/malfunction The drive is braked with the stop ramp t13/t23 (→2197).
Once the stop speed is reached, the output stage is inhib-
ited and the brake is applied.
The error is signaled immediately.
The ready signal is revoked.
A restart is only possible after a fault reset has been per-
formed during which the device is reinitialized.
Immediate stop/Warn-
ing
Immediate switch-off of the device with error message.
The output stage is inhibited and the brake is applied.
The ready signal is not revoked.
The drive restarts without device re-initialization if the error
is rectified by an internal procedure or by an error reset.
Emergency stop/Warn-
ing
The drive is braked with the emergency stop ramp t14/t24
(→2197).
Once the stop speed is reached, the output stage is inhib-
ited and the brake applied.
The error is signaled immediately.
The ready signal is not revoked.
The drive restarts without device re-initialization if the error
is rectified by an internal procedure or by an error reset.
Rapid stop/Warning The drive is braked with the stop ramp t13/t23 (→2197).
Once the stop speed is reached, the output stage is inhib-
ited and the brake applied.
The error is signaled immediately.
The ready signal is not revoked.
The drive restarts without device re-initialization if the error
is rectified by an internal procedure or by an error reset.
P540 Response to vibration/warning
Factory setting: Display error
If the drive vibration sensor signals a warning, the device carries out the set response.
P541 Response to vibration/fault
Factory setting: Rapid stop/Warning
If the drive vibration sensor signals an error, the device carries out the set response.
P542 Response oil aging/warning
Factory setting: Display error
If the oil aging sensor signals a warning, the device carries out the set response.
P543 Response oil aging/fault
Factory setting: Display error