13
Parameter setting
Parameter descriptions
Manual – MOVIPRO
®
with EtherNet/IP™ or Modbus/TCP Fieldbus Interface
211
P53. Motor temperature protection
P530 Sensor type 1
AUTO
Setting range: No Sensor/ TF/TH/ TF/TH DEU/ KTY/ KTY DEU
Selection of the sensor used for motor protection in parameter set 1
Setting "TF/TH": Set the response with P835 Response ’TF-Message’ (→2226).
"KTY" setting: Can only be selected for synchronous motors from
SEW‑EURODRIVE. Activate the motor model with the setting "One servomotor" of
the parameter P340 Motor protection 1 (→ 2 205). Set the response with the
parameter P832 Response ’Motor overload' (→2225).
P531 Sensor type 2
AUTO
Setting range: No Sensor/ TF/TH
Selection of the sensor used for motor protection in parameter set 2
P54. Gear unit/motor monitoring
These parameters are used to set the response to be triggered in the event of a motor
or gear unit problem. The binary inputs must be programmed with the corresponding
function. The error responses are also be triggered in the "controller inhibit" device
status.
The following table shows possible error responses:
Response Description
No response An error is not displayed, nor is an error response per-
formed. The signaled error is ignored.
Display error Display of error on the 7-segment display of the device and
in the MOVITOOLS
®
MotionStudio engineering software.
The device performs no other error responses.
The device can be reset by a device reset (terminal, field-
bus, auto reset).
Immediate stop/mal-
function
Immediate switch-off of the device with error message.
The output stage is inhibited and the brake is applied.
The ready signal is revoked.
A restart is only possible after a fault reset has been per-
formed during which the device is reinitialized.
Emergency stop/mal-
function
The drive is braked with the emergency stop ramp t14/t24
(→2197).
Once the stop speed is reached, the output stage is inhib-
ited and the brake is applied.
The error is signaled immediately.
The ready signal is revoked.
A restart is only possible after a fault reset has been per-
formed during which the device is reinitialized.
16998413/EN – 12/2016