13
Parameter setting
Parameter descriptions
Manual – MOVIPRO
®
with EtherNet/IP™ or Modbus/TCP Fieldbus Interface
226
P835 Response to "TF signal"
Factory setting: No response
Triggered via the temperature sensor monitoring of the temperature sensor TF or TH
in the motor winding, as applicable.
P836 Response 'Timeout SBus1'
Factory setting: Emergency stop/malfunction
Triggered via the system bus timeout monitoring.
P838 Response 'SW limit switch'
Factory setting: Emergency stop/malfunction
This response is triggered if a target position outside the software limit switch is spe-
cified in the referenced drive. The software limit switches are set using parameters
P920/P921 SW limit switch CW/CCW (→2237).
P839 Response to "Positioning interruption"
Factory setting: No response
If the parameter P924 'Position interruption' detection (→2238) is activated, this re-
sponse is triggered upon interrupting a positioning process.
P84. Reset behavior
P840 Manual reset
Setting range: Yes/No
• Set to "Yes": Resets the error in the power section "PFA-...". As soon as the reset
is carried out, the parameter automatically resets to the setting "No". Activating the
manual reset does not have any effect if there is no error present.
• Set to "No": No reset is performed.