13
Parameter setting
Parameter descriptions
Manual – MOVIPRO
®
with EtherNet/IP™ or Modbus/TCP Fieldbus Interface
227
P841 Auto reset
Setting range: On/Off
DANGER
Risk of crushing if the motor starts up automatically after an auto reset.
Fatal or severe injuries and damage to property.
Do not use the auto-reset function with drives where an automatic restart could
represent a danger to people or devices.
Perform a manual reset.
Setting "On": Automatically performs a device reset in case of error after an ad-
justable wait period. The wait period is adjusted via the parameter P842 Restart
time (→2227).
A maximum of 5 auto resets are possible during an auto reset phase. If 5 errors
occur that are reset by an auto-reset, no more auto-resets are possible until one of
the following situations occurs:
A manual reset is performed using the input terminal
A manual reset is performed via the serial interface (with the
MOVITOOLS
®
MotionStudio engineering software or via the PLC)
There is a transition to 24 V backup mode, or the device is switched off com-
pletely
Five automatic resets are then possible again.
Setting "Off": No auto reset is performed.
P842 Restart time
Setting range: 1–3–30s
Wait time that should occur between the moment an error occurs and the execution of
an automatic reset.
P85. Scaling actual speed value
Specifies a user-specific display parameter. The display parameter is shown in the
parameter P001User display (→2191).
Example
A scaling factor of 1/60 is required to display the actual speed value in s
-1
. The follow-
ing settings must be specified for the display parameter:
Parameter Setting
P850 Scaling factor numerator 1
P851 Scaling factor denominator 60
P852 User unit s
-1
With these settings, an actual speed value of 1500 min
-1
in the parameter P001 User
display is shown as 25s
-1
.
16998413/EN – 12/2016