14
Service
List of power section errors
Manual – MOVIPRO
®
with EtherNet/IP™ or Modbus/TCP Fieldbus Interface
252
Code Meaning Response
(P)
Sub-
code
Meaning Possible cause Measure
25 EEPROM Rapid stop 0 Read or write
error on
EEPROM power
section
Error while accessing
EEPROM
Restore factory
settings, perform
reset and reset
parameters
Contact
SEW‑EURODRIVE
Service if the error
reoccurs
11 NV memory read
error
Internal NVRAM
13 NV memory chip
card
System module
defective
14 NV memory chip
card
Memory card de-
fective
16 NV memory ini-
tialization error
26 External
terminal
Emergency
stop (P)
0 External terminal Read external error
signal via program-
mable input
Eliminate respective
cause; reprogram ter-
minal if necessary
27 No limit
switches
Emergency
stop
0 Limit switches
missing or wire
break
Open circuit/both
limit switches miss-
ing
Limit switches are
swapped over in
relation to direction
of rotation of motor
Check wiring of
limit switches
Swap limit switch
connections
Reprogram termin-
als
2 Limit switches re-
versed
3 Both limit
switches are act-
ive simultan-
eously
29 Limit
switch
reached
Emergency
stop
0 HW limit switch
reached
A limit switch has been
reached in IPOS
plus®
operating mode (only
with application
module).
Check travel range
Correct user pro-
gram
30 Emergency
stop
timeout
Immediate
stop
0 Timeout stop
emergency stop
rate
Drive overloaded
Emergency stop
ramp too short
Check configura-
tion
Extend emergency
stop ramp
16998413/EN – 12/2016