14
Service
List of power section errors
Manual – MOVIPRO
®
with EtherNet/IP™ or Modbus/TCP Fieldbus Interface
261
Code Meaning Response
(P)
Sub-
code
Meaning Possible cause Measure
111 Internal
"Timeout"
error
Rapid stop/
warning
0 Communication
error with the
power section
Not able to establish a
connection with the
"PFA-..." power sec-
tion (connection
failed).
When using the ap-
plication module
"Transparent3PD"
In
MOVITOOLS
®
MotionStudio
, right-click the
device.
Choose [Applica-
tion modules] >
[Application Con-
figurator].
Choose [Open
configuration from
controller]. Check
the following set-
tings, and adjust
them, if necessary:
Controller inter-
face=SBUS_1
Axis address =
20
Device type
=MOVIPROLT
When using other
application modules
In
MOVITOOLS
®
MotionStudio
, right-click the
power section of
your device.
Choose [Techno-
logy Ed-
itor]>[Drive start-
up for MOVI‑PLC/
CCU] and start up
the drive.
116 The existing connec-
tion to the "PFA-..."
power section was in-
terrupted.
16998413/EN – 12/2016