5
Installation notes
Connection to the Ethernet network
Manual – MOVIPRO
®
with EtherNet/IP™ or Modbus/TCP Fieldbus Interface
37
Code Meaning Possible cause Measure
SF23 Error during data recovery,
data recovery to device failed
Controller not inhibited Set the device to one of the
following states:
Controller inhibit (A1.1)
Safe torque off (A1.U)
SF99 Internal system error
SF110 Actuator voltage overload
error
Actuator voltage overload Check the cabling of the di-
gital inputs and outputs.
SF120 Error due to overload in
sensor voltage of group 1
Overload sensor voltage
group 1
Check the cabling of the di-
gital inputs and outputs.
SF121 Error due to overload in
sensor voltage of group2
Overload sensor voltage
group 2
Check the cabling of the di-
gital inputs and outputs.
Status LEDs
The status LEDs are located on the service unit. They show the fieldbus and device
status.
[1]
1954344587
[1] Status LEDs S1, S2, S3
Status LED S1 EtherNet/IP™ and Modbus/TCP
Status LED Meaning
Off The device does not yet have any IP parameters.
Flashing
green/red
The device performs an LED test.
Flashing
green
There is no controlling I/O connection.
Lights up
green
There is a controlling EtherNet/IP™ I/O connection.
Lights up red A conflict has been detected in the assigned IP addresses. Another
node in the network uses the same IP address.
Flashing red The previously established controlling I/O connection is in timeout
state. The state is reset by restarting communication.
16998413/EN – 12/2016