6
Configuration and startup of EtherNet/IP™
Project planning examples
Manual – MOVIPRO
®
with EtherNet/IP™ or Modbus/TCP Fieldbus Interface
50
6.5.2 MOVIPRO
®
as speed-controlled drive–configuring process data exchange
The following example describes the configuration of the process data exchange
between an EtherNet/IP™ master (PLC) and MOVIPRO
®
as speed-controlled drive in
Studio 5000 Logix Designer.
INFORMATION
This description applies for all versions of the programming software from Rockwell
Automation (RSLogix 5000, from version 20: Studio 5000 Logix Designer).
Proceed as follows:
1. Start the device as a speed-controlled drive (→225). No application module is
used in this configuration.
2. Set the IP address parameters of the device (→229).
3. Include the device in the configuration for the "I/O Configuration" in Studio 5000
Logix Designer with 5 process data words (→240).
4. Create a user-defined data type. It allows you to organize the process data in a
structure and simplifies access to the data elements.
9007201224042635
5. Enter the description of the function of the device and internal power section
"PFA-..." in the "Description" edit box.