7
Ethernet Industrial Protocol (EtherNet/IP™)
CIP object directory
Manual – MOVIPRO
®
with EtherNet/IP™ or Modbus/TCP Fieldbus Interface
83
7.4.7 TCP/IP interface object
Allows for configuration of the IP parameters via EtherNet/IP™.
Class code: F5
hex
Class
Attrib-
ute
Ac-
cess
Name Data type Default value
hex
Description
1 Get Revision UINT 0001 Revision 1
2 Get Max Instance UINT 0001 Maximum instance
3 Get
Number of
Instances
UINT 0001
The device has one TCP/IP inter-
face.
Instance 1
The following table provides an overview of instance 1 of the TCP/IP interface object:
Attrib-
ute
Ac-
cess
Name Data type Default value
hex
Description
1 Get Status DWORD 00000001 Valid configuration
2 Get
Configuration
Capability
DWORD 00000014
The interface configuration attribute
(5) is writable. The DHCP can be
used for configuration.
3 Set
Configuration
Control
DWORD 00000002
Value 0: The device uses IP para-
meters saved during boot-up.
Value 1: The device awaits its IP
configuration via DHCP during
boot-up.
4 Get
Physical Link
Object
STRUCT of
Reference to the EtherNet link ob-
ject (class code 0xF6) as sublayer.Path Size UINT 0002
Path Padded EPATH 20 F6 24 01
5 Set
Interface
Configuration
STRUCT of
IP Address UDINT Current IP address
Network Mask UDINT Current subnetwork mask
Gateway Address UDINT Currently set standard gateway
Name Server UDINT 00000000 DNS is not supported.
Name Server 2 UDINT 00000000 DNS is not supported.
Domain Name STRING sew.de
6 Get Host Name STRING Not used
Supported services
The following table shows the services supported by the TCP/IP interface object:
Service Code
hex
Service Name class Instance
01 Get_Attributes_All X
0E Get_Attribute_Single X X
10 Set_Attribute_Single X