EasyManua.ls Logo

Siemens 7SC80 - Page 142

Siemens 7SC80
782 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Addr. Parameter C Setting Options Default Setting Comments
1626 Recloser Curves Curve A (101)
Curve B (117)
Curve C (133)
Curve D (116)
Curve E (132)
Curve K (162)
Curve N (104)
Curve R (105)
Curve W (138)
Curve 2 (135)
Curve 3 (140)
Curve 8 (113)
Curve 8* (111)
Curve 9 (131)
Curve 11 (141)
Curve A (101) Recloser Curves
1630 M.of PU TD 1.00 .. 20.00 I/Ip; ∞
0.01 .. 999.00 TD
Multiples of PU Time-Dial
1631 I/IEp Rf T/TEp 0.05 .. 0.95 I/Ip; ∞
0.01 .. 999.00 TD
67N TOC
1634 67N-3 PICKUP 0.50 .. 30.00 A; ∞ ∞ A 67N-3 Pickup
1635 67N-3 DELAY 0.00 .. 60.00 sec; ∞ 0.00 sec 67N-3 Time Delay
1636 67N-3 Direction Forward
Reverse
Non-Directional
Forward 67N-3 Direction
1637A 67N-3 MEASUREM. Fundamental
True RMS
Fundamental 67N-3 measurement of
1638 67N-3 w. Inrush NO
YES
NO 67N-3 with Inrush Restraint
1639A 67N-3 active always
with 79 active
always 67N-3 active
1640 67N-TOC-1 Dir. Forward
Reverse
Non-Directional
Forward 67N-TOC-1 Direction
1641 67N-TOC-2 Dir. Forward
Reverse
Non-Directional
Forward 67N-TOC-2 Direction
1642 67N-TOC-3 Dir. Forward
Reverse
Non-Directional
Forward 67N-TOC-3 Direction
1643 67N-TOC-4 Dir. Forward
Reverse
Non-Directional
Forward 67N-TOC-4 Direction
1644 67N-TOC-1 PU 1A 0.05 .. 4.00 A; ∞ 1.00 A 67N-TOC-1 Pickup
5A 0.25 .. 20.00 A; ∞ 5.00 A
1645 67N-TOC-1 TD 0.01 .. 20.00 sec; ∞ 0.50 sec 67N-TOC-1 Time Dial
1646A 67N-TOC-1 MEAS. Fundamental
True RMS
Fundamental 67N-TOC-1 measurement
of
Functions
2.3 Directional Overcurrent Protection 67, 67N
142 SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017

Table of Contents