[7sj80-svs-20061219, 2, en_US]
Figure 2-107
Logic diagram of the breaker failure protection
Setting Notes
General
Breaker failure protection is only effective and accessible if address 170 50BF is set to Enabled or enabled
w/ 3I0>. Setting Enabled considers the three phase currents for total current monitoring. Setting enabled
w/ 3I0> additionally evaluates the ground current or the negative sequence system when only one phase
current occurs.
With the setting Enabled w/o I>, only the circuit breaker auxiliary contacts are evaluated. The current crite-
rion CB Icrit.closed is not included in the logic (see Figure 2-105).
If this function is not required, then Disabled is set. The function can be set to ON or OFF under address
7001 FCT 50BF.
2.18.2
Functions
2.18 Breaker Failure Protection 50BF