[7sj80_ueberlastschutz-061116, 1, en_US]
Figure 2-61
Logic diagram of the overload protection
Setting Notes
General
Overload protection is only effective and accessible if address 142 49 was set to No ambient temp. If the
function is not required, Disabled is set.
2.11.2
Functions
2.11 Thermal Overload Protection 49
SIPROTEC Compact, 7SC80, Manual 221
E50417-G1140-C486-A8, Edition 07.2017