Displacement-voltage element of the (sensitive) ground fault detection
•
Directional time overcurrent protection (phase and ground function)
•
Undervoltage protection
The voltage monitoring function works with the fundamental components of current and voltage. The nega-
tive, positive, and zero sequence voltages are derived from the line voltages; a suitable voltage transformer
connection type needs to be selected.
[anschl-spg-wdl-3phl1e-131106, 1, en_US]
Figure 2-72
Wiring for 3-phase voltage transformer connection: VAN, VBN, VCN
Functions
2.12 Monitoring Functions
SIPROTEC Compact, 7SC80, Manual 235