Addr. Parameter Setting Options Default Setting Comments
7175 51N-3 No influence
Starts 79
Stops 79
No influence 51N-3
7176 51-4 No influence
Starts 79
Stops 79
No influence 51-4
7177 51N-4 No influence
Starts 79
Stops 79
No influence 51N-4
7178 67 TOC-1 No influence
Starts 79
Stops 79
No influence 67 TOC-1
7179 67N TOC-1 No influence
Starts 79
Stops 79
No influence 67N TOC-1
7180 67 TOC-2 No influence
Starts 79
Stops 79
No influence 67 TOC-2
7181 67N TOC-2 No influence
Starts 79
Stops 79
No influence 67N TOC-2
7182 67 TOC-3 No influence
Starts 79
Stops 79
No influence 67 TOC-3
7183 67N TOC-3 No influence
Starts 79
Stops 79
No influence 67N TOC-3
7184 67 TOC-4 No influence
Starts 79
Stops 79
No influence 67 TOC-4
7185 67N TOC-4 No influence
Starts 79
Stops 79
No influence 67N TOC-4
7200 bef.1.Cy:50-1 Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 50-1
7201 bef.1.Cy:50N-1 Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 50N-1
7202 bef.1.Cy:50-2 Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 50-2
7203 bef.1.Cy:50N-2 Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 50N-2
7204 bef.1.Cy:51 Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 51