EasyManua.ls Logo

Siemens SIMATIC ET 200S - Page 150

Siemens SIMATIC ET 200S
382 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1PosInc/Analog
4.6 Functions of the 1PosInc/Analog
ET 200S Positioning
150 Operating Instructions, 05/2007, A5E00124871-04
Control Signals: Relative Positioning
Address Assignment
Bits 0.7 to 0.4:
7 6 5 4 Bit
0 1 0 0
MODE 4 = Relative Positioning
Byte 0
Bit 2: DIR_M
Bit 1: DIR_P
Bit 0: START
Bytes 1 to 3 Distance
(linear axis: 0 to 16 777 215; rotary axis: 0...16 777 215)
Feedback Signals: Relative Positioning
Address Assignment
Byte 0 Bit 3: SYNC
Bit 2: POS_ DONE
Bit 1: POS_ERR
Bit 0: POS_ACK
Bytes 1 to 3 Actual value
(linear axis: 0 to 16 777 215; rotary axis: 0 to end of rotary axis - 1)
Parameters: Relative Positioning
Parameters Meaning Value range Default setting
Drive
Switch-off
difference
Defines the distance from the destination at
which the drive is slowed down from creep feed
to 0. If the switch-off difference ≥ the switchover
difference, there is no switchover point. There is
no slowdown from rapid feed to creep feed.
0 - 65 535 100
Switchover
difference
Defines the distance from the destination at
which the drive is slowed down from rapid feed
to creep feed.
0 - 65 535 1000

Table of Contents

Other manuals for Siemens SIMATIC ET 200S

Related product manuals