Parameters Meaning Value range Default setting
Drive
Control mode Type 0 means:
DO0 travel minus
DO1 travel plus
DO2 rapid/creep feed
Type 1 means:
DO0 rapid feed
DO1 creep feed (rapid feed is 0)
DO2 travel plus (1)/minus (0)
0
1
0
T
min
direction change The digital outputs are switched off, and a
change of direction by T
min
is executed with a
delay.
T
min
is effective at each change of direction
during a run.
T
min
is not effective at startup after POS_DONE
= 1 or POS_ERR = 1.
Your input value is multiplied by 10. You thus
specify T
min
in increments of 10 ms (for
example, 0 ms, 10 ms or 2550 ms)
0 - 255 0