1PosSSI/Analog
6.3 Terminal Assignment Diagram
ET 200S Positioning
248 Operating Instructions, 05/2007, A5E00124871-04
6.3 Terminal Assignment Diagram
Wiring rules
The wires (terminals 1 and 5, 4 and 8) must be in twisted pairs and shielded. The shield
must be supported at both ends. You use the shield contact element
(Order Number: 6ES7 390-5AA00-0AA0) as a shield support.
Terminal assignment
Table 6-2 Terminal assignment of the 1PosSSI/Analog
Terminal assignment View Remarks
Connection of the SSI Encoder:
Terminals 1-8
Connection of the Switches and the
Drive: Terminals 9-16
1: D 9: IN0 Minus limit switch
5: /D
Data from the SSI
encoder
13: IN1 Plus limit switch
3: B 14: IN2 Reducing cam; latch
signal
7: /B
Unused terminals
10: 24 VDC Encoder supply for the
switches
2: 24 V DC 12: QV+
6: M
Power supply for
SSI encoder
16: M
ana
Analog output ± 10 or
0 V to 10 V to connect
the drive
4: C 11: OUT
6)
326
(6'.$%
326
83 '1
66,
&
&
'
'
/
0
66,$QDORJ
8:/C
SSI clock (clock
line)
15: M
Digital output for direct
control or as a
directional signal for
the drive
Connection of Relays and Contactors to the Digital Output
Note
Direct connection of inductivities (such as relays and contactors) is possible without external
circuiting.
If SIMATIC output circuits can be deactivated by additionally installed contacts (for example
relay contacts), you have to provide additional overvoltage protection devices at inductivities
(see the following example for overvoltage protection).