EasyManuals Logo

Siemens SIMATIC ET 200S Operating Instructions

Siemens SIMATIC ET 200S
382 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #105 background imageLoading...
Page #105 background image
1PosInc/Digital
3.8 Parameter List
ET 200S Positioning
Operating Instructions, 05/2007, A5E00124871-04
105
3.8 Parameter List
Overview
Parameters Meaning Value range Default setting
Enables
Group diagnostics When group diagnostics is enabled, an encoder
error (ERR_ENCODER), no load voltage
(ERR_2L+) or a parameter assignment error will
result in a channel-specific diagnostics.
• Disable
• Enable
Disable
Encoder signal
diagnostics
Encoder signals A, /A and B, /B are monitored for
short circuit and wire break.
• On
• Off
On
Zero marker diagnostics Zero marker signals N, /N are monitored for short
circuit and wire break.
• On
• Off
On
Axis
Reversal of the direction
of rotation
Adjustment of the direction of rotation of the
encoder
• Off
• On
Off
Axis type Selection of linear axis without limitation or rotary
axis with overrun/underrun at end of rotary axis
• Linear
• Rotary
Linear
End of rotary axis Only relevant for rotary axis type:
Underrun: 0 to end of rotary axis - 1
Overrun: End of rotary axis - 1 to 0
Parameter assignment error at 0
1 - 16 777 215 36 000
Digital Inputs
DI0 limit switch minus Switch on the DI0 digital input is a break or make
contact
• Break contact
• Make contact
Break contact
DI1 limit switch plus Switch on the DI1 digital input is a break or make
contact
• Break contact
• Make contact
Break contact
DI2 reducing cam Switch on the DI2 digital input is a break or make
contact
• Break contact
• Make contact
Make contact
Reference point run and evaluation of the reference signal
Reference signal This parameter defines the relevant switch or the
combination of switch and zero mark.
• Reference switch
and zero mark
• Reference switch
• Zero mark
Reference switch
and zero mark
Reference switch Relevant in the case of reference signal:
• Reference switch and zero mark
• Reference switch
This parameter defines the referencing direction in
which the switch must be traversed.
• Reduction cam
towards minus
• Reduction cam
towards plus
• Minus limit switch
• Plus limit switch
Reduction cam
towards minus
Start direction of the
reference point run
• Plus
• Minus
Plus

Table of Contents

Other manuals for Siemens SIMATIC ET 200S

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200S and is the answer not in the manual?

Siemens SIMATIC ET 200S Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC ET 200S
CategoryI/O Systems
LanguageEnglish

Related product manuals