1PosSSI/Digital
5.10 Technical specifications
ET 200S Positioning
238 Operating Instructions, 05/2007, A5E00124871-04
5.10 Technical specifications
Overview
Technical Data of the 1PosSSI/Digital
Dimensions and weight
Dimension W x H x D (mm) 30 x 81 x 52
Weight Approx. 65 g
Data for specific modules
Number of channels 1
Voltages, currents, potentials
Rated load voltage L+
Range
P1
24 VDC
20,4 ... 28.8 V
Yes
Isolation
Between the backplane bus and the I/O
Yes
Sensor supply
Output voltage
Output current
L+ -0.8 V
Maximum 500 mA, short-circuit proof
Current consumption
From the backplane bus
From the load voltage L+ (no load)
Max. 10 mA
Max. 50 mA
Power dissipation Typ. 2 W
Data for the digital inputs
Input voltage
Rated value
0 signal
1 signal
24 VDC
-30 V to 5 V
11 V to 30 V
Input current
0 signal
1 signal
≤ 2 mA (perm. leakage current)
9 mA (typ.)
Minimum pulse width 500 µs
Connection of a two-wire BERO Type 2 Possible
Input characteristic curve To IEC 1131, Part 2, Type 2
Length of cable 50 m