ET 200S Positioning
Operating Instructions, 05/2007, A5E00124871-04
189
1PosSSI/Digital
5
5.1 Product overview
Order number
6ES7138-4DH00-0AB0
Features
Positioning module for controlled positioning by means of rapid/creep feed
Switchover and switch-off difference can be set using your control program
SSI Encoder
13-bit Singleturn
25-bit Multiturn
Usable axis types:
Linear axis
Rotary axis
Operating range: 0 - 16 777 215 steps
The drive can be controlled via 3 digital outputs:
Travel minus
Travel plus
Rapid/creep feed
3 digital inputs can be used for the following:
Minus hardware limit switch
Plus hardware limit switch
Latch signal
Diagnostics
Encoder monitoring
Load voltage monitoring