EasyManua.ls Logo

Siemens SIMATIC ET 200S - Technical Specifications for the 1 Posinc;Analog

Siemens SIMATIC ET 200S
382 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1PosInc/Analog
4.10 Technical Specifications for the 1PosInc/Analog
ET 200S Positioning
184 Operating Instructions, 05/2007, A5E00124871-04
4.10 Technical Specifications for the 1PosInc/Analog
Overview
Technical Data of the 1PosInc/Analog
Dimensions and weight
Dimension W x H x D (mm) 30 x 81 x 52
Weight Approx. 65 g
Data for specific modules
Number of channels 1
Voltages, currents, potentials
Rated load voltage L+
Range
P1
24 VDC
20.4 ... 28.8 V
Yes
Isolation
Between the backplane bus and the I/O
Between analog output and load voltage L+
Yes
Yes
Permissible potential difference between M
ANA
and
the central grounding point U
iso
75 V DC/60 V AC
Insulation tested 500 VDC
Sensor supply
Output voltage
Output current
L+ -0.8 V
Maximum 500 mA, short-circuit proof
Current consumption
From the backplane bus
From the load voltage L+ (no load)
Max. 10 mA
Max. 50 mA
Power dissipation Typ. 2 W
Data for the digital inputs
Input voltage
Rated value
0 signal
1 signal
24 VDC
-30 V to 5 V
11 V to 30 V
Input current
0 signal
1 signal
≤ 2 mA (perm. leakage current)
9 mA (typ.)
Minimum pulse width 500 µs
Connection of a two-wire BERO Type 2 Possible
Input characteristic curve To IEC 1131, Part 2, Type 2
Length of cable 50 m