1PosInc/Analog
4.10 Technical Specifications for the 1PosInc/Analog
ET 200S Positioning
Operating Instructions, 05/2007, A5E00124871-04
185
Technical Data of the 1PosInc/Analog
Data on the Digital Output
Output voltage
Rated value
0 signal
1 signal
24 VDC
≤ 3 V
≥ L+ -1 V
Output current
0 signal (leakage current)
1 signal
Rated value
Permitted range
≤ 0.3 mA
0.5 A
7 mA to 0.6 A
Switch rate
Resistive load
Inductive load
Lamp load
100 Hz
2 Hz
≤ 10 Hz
Lamp load ≤5 W
Output delay (resistive load, output current 0.5 A)
At 0 to 1
At 1 to 0
typ. 150 µs
typ. 150 µs
Short-circuit protection of the output Yes
Threshold on 0.7 A to 1.8 A
Inductive extinction Yes; L+ -(55 to 60 V)
Digital input control Yes
Cable lengths
Unshielded
Shielded
600 m
1000 m
Data for the Analog Output
Resolution (including overrange) ± 10 V/13 bits + sign
Settling time
For resistive load
For capacitive load
For inductive load
0,1 ms
0.5 ms
0.5 ms
Length of cable
Shielded
Max. 100 m