4.10 Technical Specifications for the 1PosInc/Analog
ET 200S Positioning
186 Operating Instructions, 05/2007, A5E00124871-04
Technical Data of the 1PosInc/Analog
Suppression of interference, limits of error
Operational limit (in the entire temperature range,
with reference to the output range)
± 0.4 %
Basic error limit (operational limit at 25°C with
reference to output range)
± 0.2 %
Temperature error (with reference to the output
range)
± 0.01 %/K
Linearity error (with reference to the output range) ± 0.02 %
Repeatability (in steady state at 25°C with
reference to output range)
± 0.05 %
Output ripple (with reference to output range,
bandwidth 0 to 50 kHz)
± 0.02 %
Data for selecting an actuator
Output range (rated value) ±10 V
Load resistance
• For capacitive load
• Short-circuit protection
• Short-circuit current
Min. 1.0 kΩ
Max. 1 µF
Yes
Approx. 25 mA
Destruction limit against voltages/currents applied
from outside
• Voltage at the outputs to M
ANA
• Current
Max. 15 V continuous; 75 V for max. 1 s
(pulse duty factor 1/20)
Max. DC 50 mA
Connection of actuators
• 2-conductor connection
No compensation for surge impedance
Encoder signals
Level
• Terminating resistance
• Differential input voltage
• Max. frequency
To RS 422
330 Ω
Min. 1 V
500 kHz
Length of cable
• Shielded
Max. 50 m
Status, Diagnostics
Change in actual value (up) UP LED (green)
Change in actual value (down) DN LED (green)
Status display positioning in operation LED POS (green)
Status display DI0 (minus hardware limit switch) LED 9 (green)
Status display DI1 (plus hardware limit switch) LED 13 (green)
Status display DI2 (reducing cam) LED 14 (green)
Group error on the 1PosInc/Analog SF LED (red)
Diagnostic information Yes