1PosUniversal/Digital
7.6 Functions of the 1PosU
ET 200S Positioning
366 Operating Instructions, 05/2007, A5E00124871-04
Causes of Errors for JOB_ERR
Table 7-4 Causes of Errors for JOB_ERR
Error Number Meaning Remedy
21 JOB unknown or impermissible Permissible JOBs are:
• JOB 0
• JOB 1
• JOB 2 (only possible at SSI encoders)
• JOB 3
• JOB 4
• JOB 9 (not possible at SSI encoders or in
dosing operation)
• JOB 10
• JOB 11 (not possible in dosing operation)
• JOB 15
23 ERR_ENCODER is displayed Check the encoder wiring
26 JOB 2 (move encoder range) cannot be initiated
because there is an active run
29 Evaluating the Reference Signal: Reference point
coordinates ≥ end of rotary axis
34 Setting an Actual Value: Actual value coordinates
≥ encoder range
35 Display current values: Selection unknown
36 Latch Function: Edge selection unknown
37 Display current values: JOB 15 cannot be
activated with the latch function running.
38 Monitoring of the direction of rotation
Path difference > 65 535