4.7 CPU /Master Stop and RESET State
ET 200S Positioning
176 Operating Instructions, 05/2007, A5E00124871-04
4.7 CPU/Master Stop and RESET State
Behavior at CPU-Master-STOP
Behavior at CPU-Master-STOP Response of the 1PosInc/Analog
Due to power-off of the CPU/DP master
or
Due to power-off of the IM 151/ IM 151 FO
or
Due to failure of DP transmission
or
Due to change from RUN to STOP
The current run is stopped.
Analog output QV+ is set to 0 V
Digital output:
if the direction is assigned parameters for the DO
function, the digital output OUT=0 is set
Feedback bit POS_ERR = 0
Feedback bit POS_DONE = 1
Exiting the CPU-Master-STOP Status
Exiting the CPU-Master-STOP Status Response of the 1PosInc/Analog
At power-on of the CPU/DP master
or
At power-on of the IM 151/ IM 151 FO
or
After failure of the DP transmission
or
After a change from STOP to RUN
The feedback interface of the 1PosInc/Analog remains
current.
The axis remains synchronized, and the actual value is
current.
The following changed values remain valid:
Voltage for rapid feed
Voltage for creep feed
Acceleration (T
acc
)
Deceleration T
dec
Switch-off and switchover difference
The path difference for the monitoring of the direction of
rotation
remains valid.
An initiated JOB 9: Evaluating the Reference Signal and JOB
10: Latch function remains active.
The feedback bit selected with JOB 15 is current.