1PosInc/Analog
4.7 CPU /Master Stop and RESET State
ET 200S Positioning
Operating Instructions, 05/2007, A5E00124871-04
177
RESET State of the 1PosInc/Analog
RESET Status of the 1PosInc/Analog and Changing the
Parameters of the 1PosInc/Analog
Response of the 1PosInc/Analog
• Changing the parameters of the 1PosInc/Analog and
downloading the parameter assignment and
configuration of the ET 200S station to the CPU/DP
master
or
• Power-on at the power module of the
1PosInc/Analog
or
• Inserting the 1PosInc/Analog in an energized state
• The axis is not synchronized and the actual value = 0.
• The voltage for rapid feed is set to 10 V.
• The voltage for creep feed is set to 1 V.
• Acceleration (T
acc
) and deceleration (T
dec
) are transferred
from the parameters.
• The switch-off and switchover difference is accepted from
the parameters.
• The path difference for the monitoring of the direction of
rotation is set at double the switch-off difference.
• JOB 9: Evaluating the Reference Signal and JOB 10: Latch
function are not active.
• The residual distance is displayed as a feedback value.