1PosInc/Digital
3.3 Terminal Assignment Diagram
ET 200S Positioning
Operating Instructions, 05/2007, A5E00124871-04
59
3.3 Terminal Assignment Diagram
Wiring rules
The wires to the incremental encoder (terminals 1 and 5, 3 and 7 and 4 and 8) have to be in
twisted pairs and shielded. The shield must be supported at both ends. You use the shield
contact element (Order Number: 6ES7 390-5AA00-0AA0) as a shield support.
Terminal assignment
The following figure shows you the terminal assignment for the 1PosInc/Digital:
Terminal assignment View Remarks
Connection of the Incremental
Encoder with 5 V Differential
Signals: Terminals 1-8
Connection of the Switches and the
Drive: Terminals 9-16
1: A 9: IN0 Minus limit switch
5: /A
Track A
13: IN1 Plus limit switch
3: B 14: IN2 Reducing cam;
latch signal
7: /B
Track B
10: DC24 Encoder supply for
the switches
2: DC24 11: OUT0 Travel minus or
rapid feed
6: M
Voltage supply for
incremental encoder
12: OUT1 Travel plus or creep
feed
4: N 16: OUT2 Rapid/creep feed
and travel
plus/minus
326
,QF'LJLWDO
(6'*$%
326
83 '1
,QF
$
$
'&9
0
%
%
1
1
8: /N
Track N; optional
zero mark
15: 2L+ Load voltage infeed
for OUT0, OUT1
and OUT2
Connection of Relays and Contactors to the Digital Outputs
Note
Direct connection of inductivities (such as relays and contactors) is possible without external
circuiting.
If SIMATIC output circuits can be deactivated by additionally installed contacts (for example
relay contacts), you have to provide additional overvoltage protection devices at inductivities
(see the following example for overvoltage protection).