1STEP 5V/204kHz
2.9 Technical specifications
ET 200S Positioning
Operating Instructions, 05/2007, A5E00124871-04
51
2.9 Technical specifications
Technical specifications
Technical data 1STEP5V/204khZ
Dimensions and weight
Dimensions W × H × D (mm) 15 × 81 × 52
Weight Approx. 40 g
Data for specific modules
Number of channels 1
Voltages, currents, potentials
Rated load voltage L+
24 VDC
Range
20,4 ... 28.8 V
P1
Yes, as of Version 2
Isolation
Between the backplane bus and the
positioning function
Yes
Between the positioning function and
load voltage
No
Sensor supply
Output voltage
L+ (-0.8 V)
Output current
Maximum 500 mA, short-circuit proof
Current consumption
From the backplane bus
Max. 10 mA
From the load voltage L+ (no load)
Typ. 40 mA
Power dissipation of the 1STEP 5V/204kHz Typ. 1.5 W
Data for the digital inputs
Isolation No, from shield only
Input voltage
Rated value
24 VDC
0 signal
-30 ... 5 V
1 signal
11 ... 30 V
Input current
0 signal
Max. 2 mA (bias current)
1 signal
9 mA (typically)
Input delay Typically 4 ms
Connection of a two-wire BERO Type 2 Possible
Input characteristic curve To IEC 1131, Part 2, Type 2
Length of cable
Shielded
Max. 1000 m
Unshielded
Max. 600 m